The MSTR Instruction
28
840 USE 115 00 Version 1.0
Middle Node
Content
The 4x re
ister entered in the middle node is the first in a
roup of conti
uous
holdin
re
isters that comprise the
data area
. For operations that provide the
communication processor with data such as a Write operation, the
data area
is the
source of the data. For operations that ac
uire data from the communication
processor, such as a Read operation, the
data area
is the destination for the data.
In the case of the Ethernet Read and Write CTE operations
see sections 3.2.11
and 3.2.12
, the middle node stores the contents of the Ethernet confi
uration
extension table in a series of re
isters.
Bottom Node
Content
The inte
er value entered in the bottom node specifies the
length
- the maximum
number of re
isters in the
data area
. The
length
must be in the ran
e 1 ... 100.
3.2.3 MSTR Function Error Codes
If an error occurs durin
an MSTR operation, a hexadecimal error code will be
displa
ed in the first implied re
ister in the
control block
the top node
. Function
error codes are network-specific.
TCP/IP Ethernet
Error Codes
An error in an MSTR routine over TCP/IP Ethernet ma
produce one of the
followin
errors in the MSTR
control block
:
Register Content
Displayed
Identifies one of ten MSTR operations le
al for TCP/IP
(1 ... 4 and 7 ... 12).
First implied Displays error status.
Second implied Displays len
th (number of re
isters transferred).
Third implied Displays MSTR operation-dependent information.
Fourth implied Hi
h byte: Destination index.
Low byte: Quantum backplane slot address of the web
embedded server module.
Fifth implied Byte 4 of the 32-bit destination IP Address.
Sixth implied Byte 3 of the 32-bit destination IP Address.
Seventh implied Byte 2 of the 32-bit destination IP Address.
Ei
ht implied Byte 1 of the 32-bit destination IP Address.
Comments to this Manuals